1、英文文献英文文献2附录附录 1 1:外文资料翻译:外文资料翻译A1.2 原文TRANSFORMER1. INTRODUCTIONThe high-voltage transmission was need for the case electrical power is to be provided at considerable distance from a generating station. At some point this high voltage must be reduced, because ultimately is must supply a load. The tr
2、ansformer makes it possible for various parts of a power system to operate at different voltage levels. In this paper we discuss power transformer principles and applications.2. TOW-WINDING TRANSFORMERSA transformer in its simplest form consists of two stationary coils coupled by a mutual magnetic f
3、lux. The coils are said to be mutually coupled because they link a common flux.In power applications, laminated steel core transformers (to which this paper is restricted) are used. Transformers are efficient because the rotational losses normally associated with rotating machine are absent, so rela
4、tively little power is lost when transforming power from one voltage level to another. Typical efficiencies are in the range 92 to 99%, the higher values applying to the larger power transformers.The current flowing in the coil connected to the ac source is called the primary winding or simply the p
5、rimary. It sets up the flux in the core, which varies periodically both in magnitude and direction. The flux links the second coil, called the secondary winding or simply secondary. The flux is changing; therefore, it induces a voltage in the secondary by electromagnetic induction in accordance with
6、 Lenzs law. Thus the primary receives its power from the source while the secondary supplies this power to the load. This action is known as transformer action.3. TRANSFORMER PRINCIPLESWhen a sinusoidal voltage Vp is applied to the primary with the secondary open-circuited, there will be no energy t
7、ransfer. The impressed voltage causes a small current I to flow in the primary winding. This no-load current has two functions: (1) it produces the magnetic flux in the core, which varies sinusoidally between zero and m, where m is the maximum value of the core flux; and (2) it provides a component
8、to account for the hysteresis and eddy current losses in the core. There combined losses are normally referred to as the core losses.The no-load current I is usually few percent of the rated full-load current of the transformer (about 2 to 5%). Since at no-load the primary winding acts as a large re
9、actance due to the iron core, the no-load current will lag the primary voltage by nearly 90. It is readily seen that the current component Im= I0sin0, called the magnetizing current, is 90 in phase behind the primary voltage VP. It is this component that sets up the flux in the core; is therefore in
10、 phase with Im.The second component, Ie=I0sin0, is in phase with the primary voltage. It is the current component that supplies the core losses. The phasor sum of these two components represents the no-load current, orI0 = Im+ IeIt should be noted that the no-load current is distortes and nonsinusoi