汽轮发电机运行规程.doc
《汽轮发电机运行规程.doc》由会员分享,可在线阅读,更多相关《汽轮发电机运行规程.doc(13页珍藏版)》请在得力文库 - 分享文档赚钱的网站上搜索。
1、 汽轮发电机运行规程目录简介定义与缩写1 主要内容与适用范围2 STG8131-4技术规范3 发电机正常运行规定4 发电机启动试验与检查:5 发电机与系统并列和解列6 发电机励磁系统的运行与操作7 事故处理8 HSEIn briefThe CSPC facility has an internal generating capacity sufficient to meet the load requirements, and consists of four steam turbine generators and one gas turbine generator. In addition
2、 ,the connection to the utility grid provides a minimum (contractual)30MW with a reserve of 40MW(for a total of 70MW)that can be imported from the utility under emergency conditions. Based on current load ,the combination of internal generation and external supply from the Utility grid results in an
3、 N+2 sparing capacity.Normally each STG will be operating at well below the max output and generate34MW output at generator terminals ;The GTG will generate 35.74Mwpower in the mean time .Abbreviations and DefinitionsSTG Steam Turbine GeneratorAVR Automatic Voltage RegulationECR Electronic Current R
4、egulationSSPSS Substation Power Station Switchboard HSE Health Safety Environment 1 主要内容与适用范围1.1 本规程规定了STG8131-4发电机励磁机的设备规范和正常运行的要求,同时也规定了发电机启动检查与正常运行维护规定,同时并列与解列的要求及异常运行与事故处理的技术标准。1.2 本规程适用于STG8131-4全体电气运行人员及从事电气工作的有关人员。2 STG8131-4技术规范发电机型号 TLRI92/26额定视在功率 75MVA额定功率 60MW定子额定电压 11KV功率因数 0.80额定频率 50H
5、Z定子额定电流 3936A转子额定电压 224V转子额定电流 995A接线方式 YY励磁机励磁电压 98V励磁机励磁电流 78A励磁机功率 223KW极对数 1冷却水温度 43旋转二极管型号 D798N18/T18冷却方式 空冷冷却风流量 24立方米/秒冷却风温升 38.4定子绕组温升 56转子绕组温升 713 发电机正常运行规定:3.1发电机正常运行中静子电压允许在额定值的90%至110%范围内变化,但以发电机静子电流不超过额定值为准,静子电压变动时,静子电流仍以正常规定值为准。permissible operating ranges of generator:continuous oper
6、ating with rated MVA short time operating with rated MVA,continuous operating is not permissible even at reduced load.continuous operating with reduced MVA or short time operation at rated load.3.2跟踪自动功率因数和自动无功功率模式下发电机静子的电压变化情况,不应超限。3.3发电机空间加热器在发电机转速小于盘车投入转速时投入,反之,退出。3.4每班检查一次转子绕组对地绝缘。方法是:下落接地检测电刷持续
7、5秒。3.5发电机三相间电流差不得超过额定电流的10%,且任一相电流不得超过额定值,否则应降低发电机出力至允许范围。3.6发电机正常运行在额定风压下运行,若降低风压时,其运行工况必须满足下列条件:3.7发电机正常运行时,冷风温度应保持在之间,进风温度超过时,当温度每升高一度,视在功率应降低3.8 发电机并列后应对机变系统全面检查一次3.9 发电机及励磁机在额定转速下,轴承盖三个方向振动幅值的规定:3.10发电机轴承振动值不超过MM3.11励磁机轴承振动值不超过MM3.12发电机各部温度的运行规定:PARAMETEROP.VALUESETTING VALUE ALARMPROTECTIONSAT
8、OR WINDING 99130135COLD AIR TEMP.394449WARM AIR TEMP788388BEARING METAL TEMP.(TE)9095100BEARING METAL TEMP.(EE)9095100RELATIVE SHAFT VIBRATION(TE-X/Y)80um165um260umRELATIVE SHAFT VIBRATION(EE-X/Y)80um165um260um3.13 发电机进风温度变化时带负荷规定:3.14 During a long term generator shutdown check the correct operatio
9、n of the space heaters which shall be switched on when the temperature within generator is below 253.15 In case of prolonged shutdown of generator with space heaters on, stator insulation inspection must be carried out every 3 months. Without space heating ,check for presence of humidity in machine
10、and inspect stator insulation every 3 days 4 发电机启动试验与检查:4.1 启动前的试验:4.1.1 测量发电机静子回路、励磁回路绝缘应合格4.1.2 测量发电机各附属设备绝缘应合格4.1.3 SF6开关,励磁开关的拉、合试验,联锁试验,保护整组试验应良好4.1.4 试验预告信号良好4.2 启动前的检查:4.2.1检修结束后的机组电气系统的工作已全部完工,检修工作票已全部终结,为了检修设备临时加装的安全措施已全部拆除,固定安全措施恢复正常,因检修工作使用的标志牌已全部收回,并有检修交代。 4.2.2机组电气一、二次回路、励磁回路接线正确、牢固。4.2
11、.3发电机、旋转整流子外部应清洁且无损坏,进出风温度计应完整且指示正确。 4.2.4电机系统保护定值正确,保护投入正确,各微机保护完好。4.2.5电机同期回路检修后,发电机与系统的相序、相位,应由检修核对其正确性,并由书面交代。4.2.6启动前绝缘电阻值的测量4.2.6.1发电机a 发电机定子绕组在加热器投入情况下,接近工作温度时,对地及相间绝缘用2500V摇表测量,其绝缘电阻值不得低于前次测量值的b 转子绕组在冷态下(20)的绝缘,用500V摇表测量,不得低于c 发电机电阻测温元件在冷态下(20)的绝缘,用250V摇表测量d The measured insulation resistanc
12、e between bearing and the steel plate ,or between the steel plate and bearing support must not be less than 0.5 megohms under 500 V(DC) 4.2.6.2励磁机The measured insulation resistance between exciter field winding and the generator base frame must not be less than 3 megohms under 500 V(DC)4.2.7汽轮发电机组一经
13、冲转,即认为机变系统全部设备均已带电。升速过程中,值班人员应监听发电机声音应正常4.2.8发电机励磁机主变测温元件良好,数值指示正确4.2.9发电机所有VT一次保险良好4.2.10发电机冷风室内无杂物,地面干燥,冷风器无漏水。4.2.11就地消防器材齐全。4.3 发电机运行中的检查:4.3.1发电机各部温度正常且不超过规定值。4.3.2发电机各部无漏风、螺栓无松动,机壳内无异常现象和声音,振动不超过规定。4.3.3励磁装置运行正常且冷却风扇运转正常,各部指示灯及所属转换开关均应指示正确无误。4.3.4检查核对运行日志中参数变化是否正常4.3.5发电机强励动作后,应对励磁系统全面检查4.3.6封
14、闭母线温度不应超过65,微正压装置工作正常,从窥视孔检查各点无过热现象,无积水。4.3.7励磁系统运行中的检查a 励磁调节柜各表计及指示灯指示正常b 冷却风机运行正常c 各开关位置投入正确d 各部联接线正确,无松动现象5 发电机与系统并列和解列:5.1 发电机与系统并列的条件;a 发电机电压与系统电压一致;b 发电机频率与系统频率一致;c 发电机相位与系统相位一致;d 发电机相序与系统的相序一致;(相位、相序有维护人员核对正确,并有书面交代) 5.2 发电机与系统并列步骤:5.2.1检查轴承入口油压、油温正常5.2.2检查发电机空冷器已投入5.2.3发电机测量、监测、保护装置投入正常5.2.4
15、自动励磁系统做好投入准备 a 交直流动力电源送电良好 b 励磁开关操作电源已投入 c AVR及ECR上信号指示正常5.2.5接到调度命令后方可开始进行发电机与系统并列操作5.2.6转速大于盘车转速后,发电机加热器停止5.2.7发电机转速90%额定转速左右5.2.8检查轴承振动和轴承金属温度正常5.2.9合上励磁开关 5.2.10转速定速后检查定子电压升至额定5.2.11检查定、转子回路无接地5.2.12投入自动准同期装置5.2.13同期后并网带负荷 5.3发电机与系统解列;5.3.1接到调度命令后方可开始进行发电机解列操作;5.3.2将发电机有、无功负荷减至小于0.05倍额定视在功率;5.3.
16、3汽轮机调门全关;5.3.4利用发电机逆功率(第二时限10S)保护动作跳开发电机出口开关5.3.5转速滑至90%额定转速5.3.6发电机励磁开关自动跳开5.3.7冷却水系统退出5.3.8转速降至盘车投入转速后发电机空间加热器投入。5.4 发电机手动并列5.4.1 并列条件:a 发电机电压与系统电压差不大于5%b 发电机频率与系统频率差小于0.2HZc 发电机与系统的相序相同d 发电机与系统的相序一致5.4.2注意事项a同步表指针在零位停住,跳动或转动很快时,禁止合闸并列b将开关切至c同期回路维护工作完毕后,须经维护人员核对无误后,才能使用d如果按合闸按钮的同时,音响报警且开关绿灯闪光,此时应立
17、即断开开关并检查原因,待查明原因后再进行并列5.4.3发电机手动并列步骤a 接到值长可以升压命令后b 发电机转速升至90%额定转速时(AVR在自动位置)c 合上励磁开关d 检查发电机定子电压自动升至额定值且三相电压平衡e 检查定、转子回路无接地f 将准同期装置切至“手动”位置g 就地根据同期表上指示及表针转动情况手动调整定子电压和发电机转速h 当同步表转动到允许合闸范围内()时按下合闸按钮I 检查发电机出口开关已合闸并带初始负荷正常。5.5 发电机使用自动准同期装置并列5.5.1注意事项a 注意内部继电器及信号动作指示情况b 注意发电机频率的自动调整情况c 用同步表监视发电机出口开关是否同期时
18、合闸d 注意并列时发电机有无冲击5.5.2自动准同期装置的停用条件a 装置投入时,闭锁灯不亮或信号装置指示不正常b 自动装置调整失灵c 不发合闸脉冲同期装置上的升速减速升压降压合闸复位按钮在手动同期并列时使用5.5.3发电机使用自动准同期装置并列步骤a 接到值长可以升压命令后b 发电机转速升至90%额定转速时(VR在自动位置)c 合上励磁开关c 检查发电机定子电压自动升至额定电压且三相电压平衡e 检查定、转子回路无接地f 将准同期装置切至“自动”位置g 点击汽机PCS-7屏上“同期”按钮后点击汽机PCS-7屏上“启动”按钮h 检查自动准同期装置“RUNNING”灯亮I 待发电机出口开关合闸后检
19、查所带初始负荷正常5.6 机变组的破坏备用的主要内容5.6.1机变解列后破坏备用的主要操作内容 a 断开35KV母差跳发电机出口开关保护 b 将发电机出口VT主变出口VT停电 c 将励磁调节器停电 d 断开发电机出口开关及励磁开关控制电源 e 做好安全措施(将主变出口刀闸合至接地侧)5.6.2发电机变压器组恢复备用的主要内容 a 拆除安全措施 b 检查保护投入正确 c将发电机出口VT主变出口VT送电 d将励磁调节器送电 e 检查除发电机出口开关及励磁开关控制电源外的其它信号、控制电源投入良好6 发电机励磁系统的运行与操作6.1 励磁系统简介 6.1.2励磁系统有两套相对独立的控制系统组成:自动