1、528Acrel安科瑞电气AMC Series programmable intelligent metersInstallation and Operation Instruction V3.1ACREL CO.,LTD4 . 5. 3 Additional function wiringCOM of analog output and switching input represent their own common end,it is not earthing actually.Two-core shield cable is recommended for communication
2、 connection. Its wire diameter is not less than 0.5mm2 ,connecting A B respectively .shielded layer single point to connect the earth or dangling .When wiring,the communication line shall be far away from strong current cable and other strong electric field environment.For connection mode in communi
3、cation section are shown as following:Correct connection mode: Communication cable shieloing layer is connected with ground.485A485BFigure 11# LO CO 寸m LO 00 y2123222# LO CO 寸co LO 00 寸21232232# LO 00 寸CQ LD CO 寸2223RT21Two-core shielded line/ shielding layer is connected with ground.Recommendation
4、of adding matched resistance between A ,B of the last meter,the rated resistance range is 120QlOkQ.5 Operating description5.1 Key function descriptionTable 4 Key function descriptionKey symbolFunctionSET (SET)Return to previous menu or Function switchingLeft( )Same level menu shifting left or reduci
5、ng dataRight ( A)Same level menu shifting right or increasing data.Enter ( 1)Enter Next level menu or Confirm.Left+ ente V)In programming mode,this key combination is used fbr the reduction of hundreds of digits.Right + enteiA J )In programming mode,this key combination is used to increase the hundr
6、ed digits.Note: When using the combination key,you can firstly press the left or right key and then press the Enter key.5.2 Programming menu5.2.1 Menu symbol and its meaningtable 5First menuSecond menuThird menuDescription595CodE0 二 9999Password setting (initial password 0001)bLCd0-255LCD backlight
7、control,when set to O,the backlight is always on,when set to 0-255,the backlight is off after 0-255 secondsRL.-FON/OFFWhether the screen flashes when alarming/ nLi nE3P3L,3P4LElectrical network (3-phase 3-wire,3-phase 4-wire)Note: just for3 phase voltageIn. / (/ n.u)1A,5A(100 V,400V,660V)Current rat
8、ed value (Voltage rated value)ln L Jc 尸 X)09999Current ratio (Voltage ratio)H-9999-9999Full scale displayL-9999-9999Zero displayU.PRP)03Decimal point of current (voltage) displaya-99999999Shielding value of zero displaybUSRddr1-247Communication addressbRUd1.2,24,4.8,9.6,19.2,38.4Baud rate (Example 9
9、.6 means 9600bps)nodENone/2bit/odd/evenCommunication mode(No parity check,2-bit stop bit,odd parity check,even parity check)Er. /- t r.35EL123Analog output selectionE J P E420mA or 020mAOutput typeR o.H 09999High analog value settingR q.L a09999Low analog value settingd Q. i d d己_5ELO.do/l.ALAlarm s
10、election0-20Alarm delay or remote control delay (s)0-9999No action band settingNLH,0-9999High alarm value settingRLLo09999Low alarm value settingH L.- b0-100Unbalance alarm setting (%)In.zuLo.on/Lo.ofWhether alarm is allowed when the signal is 0UErVersion5.3 Setting and useThe programming example in
11、troduces some of the options in the programming menu,such as current ratio,analog output setting,and switching output setting etc.Note: After the setting or selection is completed,press the Enter key to confirm. After confirming the completion,press the SET key until the SAVE/YES page appears. At th
12、is time,you must press the Enter key to confirm,otherwise the setting is invalid.5.3.1 How to enter the programming menuSingle phase:DisplayPasswordLeft and right keys Enter thei nterfacei nterfacet enter the PasswordprOgranTn j ng j nterfaceThree phase:Press the SET key to enter Enter the password
13、with the password iinterface left or right keyThree phase:Press the SET key to enter Enter the password with the password iinterface left or right keyEnter the progranming i nterfacePS53S3S3S3S000 I5.3.2 How to save the modified parametersSingle phase:aojSETThree phase:SET丽而产黑1%*Note: You do not nee
14、d to save the parameter aftermodifying one. You can save all the parameters after modifying them as described above.5.3.3 How to modify the password,backlight time etc.Single phase:鬲用科I邺 sdf 0001e n rm rrnSUS bid 。咖E I - , JL r . e I -4U -tRkFEnter the programming menu,press left or right key to sel
15、ect the LCd page,press Enter key to enter revising condition,left or right key to modify the time to 000 255s.To LED display meter,this item is invalid.000: the LCD backlight is always on;250: the LCD backlight has no backlight after 250 seconds,and the backlight is turned off to extend the life of
16、the backlight.5.3.4 How to modify the current rated value and current ratioSingle phase:VdlUUNote: IN.I is the current rated value ,IN.U is the input voltage rated value; IN.CT is the current ratio,andIN.PT is the voltage ratio.5. 3. 5 How to modify the DC display valueThe DC voltage meter is the sa
17、me,only one difference: U.P replaces A.P;Shielding valueof zero displayWhen the zero shielding value is set to positive,it means that if | display value | W set value,the display value is 0(Fig. 6); When the set value is negative,then the display value is set value when the display value set value (
18、Fig.7).New display cuiveDC meter settingH: DC high point display value; L: DC zero point display value,A.P (U.P): Display decimal pointWhen the low point of the input is 0:For example:The input signal is 0-75mV,and the relative display needs to be 0-1000A,then the setting will be:H: 1000,L: 0,A.P: O
19、.So when the input is 37.5mV,the display will be 500 (1000-0)*(37.5/(75-0).When the low point of the input is not 0:For example: The input signal is 4-20mA,and the display needs to be 0-60.00Hz,then the chart of the relationship will be as follows:Setting: H: 6000,fiWe can get L according to the cha
20、rt: (In (H)-In (L)/In (L) = (Dis (H)-Dis (L)/ (Dis (L)-L). So L= 0 - (6000-0) * 4 / (20 - 4)= -1500.A.P:2; so when the input is 4 mA,the display will be (6000-0) * (4/20) + (-1500) = 0Hz5.3.6 How to modify the communication address,communication baud rate and communication modeSingle phase:IWtt llod
21、ify addressno orwi ww cmThree phase:Modify addressbusModify baud rate4 bU5Modify modebllS5. 3. 7 How to modify the analog output parameter,the output range and the high and low valuesTable 6tr. /First analog outputSELAnalog output selection000100020003Ul/IlU2/I2U3/I3t y PE4 20mA or 020mAR o.H tWhen
22、the analog output is 20mA,the corresponding electrical parameter is taken as the highest four-digit integer (the decimal point is ignored) and the last bit is zero.Ro.L aSame as Ao.HiSingle phase:Analog output selectionSI魏麴Modify output typefWThree phase:Modify output typeHigh value settingHigh valu
23、e setting5.3.8 How to modify the alarm item,set the alarm delay,set the high and low alarm value and the unbalance alarm setting (1 way alarm is the same as 2 way alarm)Table 7do. 1First switching outputSELAlarm settin O.do remote controlgl.AL alarmdLSWhen the SEL is 00 (remote control),DLY indicate